Napco Specs

Napco Commercial Combo. Burglary/Fire Kits

GEMC-COMBO255KT
255 Point GEM-C Commercial Combo. Fire/Burg System Kit
  • 24V Panel, 255 Points via commercial addressable, wireless or conventional fire or burg. devices, 4 on board NACs, 8 partitions (No Loop Isolator/Extender required)
  • 7 Amp, 24V Power Supply
  • Burg. Module, with power supply with built in bus isolator for complete separation of fire and burg power and battery standby operation
  • GEMC-FW-SLC Signaling Line Circuit Module--Hard-wired interface between compatible NAPCO Fire SLC devices & GEMC control panels
  • Built in horn/strobe synch. module on each NAC
  • Built in dual line communicator; dual onboard serial ports
  • Quickloader up/downloading including remote smoke obscuration reporting
  • Locking, Large Red Enclosure, 16 x 25" reversible door, with 14.25" x 25" base. Houses up to 32Ah battery backup.
  • GEMC-FK1 Red Fire Keypad--Menu-driven LCD Fire Keypad mounts anywhere on bus (Also, full keyswitch support)

  • 128 Point GEM-C Commercial Combo. Fire/Burg System Kit
    As above, but with

GEMC-COMBO128KT

  • 24V Panel, 128 Points via commercial addressable, wireless or conventional fire or burg. devices, 4 on board NACs, 8 partitions (No Loop Isolator/Extender required)
  • 4 Amp, 24V Power Supply

  • 32 Point GEM-C Commercial Combo. Fire/Burg System Kit
    Similar to above, but with

GEMC-COMBO32KT

  • 24V Panel, 32 Points via commercial addressable, wireless or conventional fire or burg. devices, 2 on board NACs, 8 partitions (No Loop Isolator/Extender required)
  • 4 Amp, 24V Power Supply

Napco Commercial Fire Kits

GEMC-FW-255KT
255 Point GEM-C Firewolf™ 24V Commercial Fire System Kit
  • 24V Panel, 255 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power
  • 7 Amp, 24V Power Supply
  • GEMC-FW-SLC Signaling Line Circuit Module--Hard-wired interface between compatible NAPCO Fire SLC devices & GEMC control panels
  • Built in horn/strobe synch. module on each NAC
  • Built in dual line communicator; dual onboard serial ports
  • Quickloader up/downloading including remote smoke obscuration reporting
  • Locking, Large Red Enclosure, 16 x 25” reversible door, with 14.25” x 25” base. Houses up to 32Ah battery backup.
  • GEMC-FK1 Red Fire Keypad--Menu-driven LCD Fire Keypad mounts anywhere on bus. (Also, full keyswitch support)

  • 128 Point GEM-C Firewolf 24V Commercial Fire System Kit
    As above, but with
GEMC-FW-128KT
  • 24V Panel, 128 Points via commercial addressable, wireless or conventional fire devices, 4 on board NACs providing up to 6.5A notification power

  • 32 Point GEM-C Firewolf 24V Commercial Fire System Kit
    Similar to above, but with
GEMC-FW-32KT
  • 24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices, 2 on board NAC's
  • 4 Amp, 24V Power Supply
  • Locking, Medium Red Enclosure, 16 x 17" door, with 14.25" x 16" base. Houses up to 16Ah battery backup.

  • 32pt GEMC Conventional Commercial Fire System Kit, ideal for sprinkler/waterflow apps. 24V Panel, 32 Points via commercial addressable, wireless or conventional fire devices, 2 on board NACs
GEMC-FW32CONVKT
  • Locking, Medium Red Enclosure, 16 x 17" door, with 14.25" x 16" base. Houses up to 16Ah battery backup.
  • 4 Amp, 24V Power Supply
  • Conventional 8-zone 2-wire fire input module, for conventional 2-wire smokes or any conventional fire detection device (GEMC-F8ZCPIM)
  • Built in horn/strobe synch. module on each NAC
  • Built in dual line communicator; dual onboard serial ports
  • Quickloader up/downloading including remote smoke obscuration reporting (for addressable detectors)
  • Menu-driven LCD Fire Keypad mounts anywhere on bus (GEMC-FK1)

Napco Commercial Burglary Kit

96pt GEMC Addressable Commercial Burglary System Kit 24V Panel, 96 Points via commercial addressable, wireless or conventional burg. devices, 7 partitions

GEMC-BURG96KT
  • Locking, Medium White Enclosure, 16 x 17” door, with 14.25” x 16” base. Houses up to 16Ah battery backup.
  • 4 Amp, 24V Power Supply
  • Addressable SLC Burg Module, supports up to 96 addressable SLC burg devices (GEMC-BSLC)
  • Built in dual line communicator; dual onboard serial ports
  • Quickloader up/downloading
  • Menu-driven LCD Burglary Keypad with built-in 4 zone EZM, mounts anywhere on bus (GEMC-BK1)

Commercial Fire & Burglary Accessories and Options

GEMC-BM/PS
  • Burg Module with 12V power supply provides isolated 4-wire burg bus for burg keypads and devices, plus 12V power output for aux. devices. Independent Burg. Bell output. Complete separation of fire and burg power, plus indep. burg. battery connection and charger for indep. burg. standby operation in power failure.
GEMC-BM
  • Burg Module, isolated 4-wire burg bus for burg keypads and devices, plus 12V power output for aux devices. Indep. Burg bell output.
GEMC-FW-SLC
  • Addressable SLC Fire Module, supports up to 128 addressable SLC fire devices. Up to 2 connect to GEM-C panel.
GEMC-BSLC
  • Addressable SLC Burg Module, supports up to 128 addressable SLC burg devices. Up to 2 connect to GEM-C panel.
GEMC-F8ZCPIM
  • Conventional 8-zone 2-wire fire input module. Plugs into GEM-C panel, for conventional 2-wire smokes or any conventional fire detection device.

Burglary Peripherals

GEMC-BK1
  • LCD Burglary Keypad for Combo. System, with 4-zone EZM built in (Requires GEMC-BM or BM/PS Module.)
GEMC-BSLC-4PT
  • Addressable SLC 4 point input expansion module
GEMC-BSLC-1PT
  • Addressable SLC 1 point input expansion module
GEMC-BSLC-DT
  • Addressable SLC Commercial Dual Tech Microwave/PIR, 40 x 40'
GEMC-BSLC-PIR
  • Addressable SLC Commercial PIR, 50 x 50'
GEMC-BSLC-RLY
  • Addressable SLC Commercial 1 point output module
GEMC-WL-PIR
  • Gemini Commercial Wireless PIR, 50 x 50'
GEMC-WL-GB
  • Gemini Commercial Wireless Glassbreak, Acoustic 25'
GEMC-WL-DT
  • Gemini Commercial Wireless Dual Tech Microwave/PIR, 40 x 40'

Fire Peripherals

GEMC-FK1
  • LCD Fire Red Keypad
GEMC-WL-SMK
  • Gemini Commercial Wireless Smoke, Photoelectric
GEMC-WL-HEAT
  • Gemini Commercial Wireless Heat, 135º F

Common Peripherals – For Commercial Fire and/or Burglary Systems

GEMC-WL-WD
  • Gemini Comml Wireless slim profile 1-input wireless module
GEMC-WL-WD2
  • Gemini Comml Wireless 2-input module converts any UL listed device into a UL wireless device (ex., pull stations or sprinkler supervisories.)
GEMC-REVC
  • Gemini Commercial Wireless 255 point RF Receiver (up to 4 per system, max.)
GEMC-EZM8
  • 8-point expansion module
GEMC- FPRINT
  • Parallel printer module
GEMC-RM3008
  • 8 Form C Relay Output Module
GEMC-NL-MOD
  • Internet Reporting Module
GEMC-RS232
  • RS232 Adapter for serial output from GEMC Panel
GEMC-OUT8
  • PGM Output Module, 8 open collector PGM outputs
GEMC-KOTamperKT
  • Merchantile Tamper Kit, for large panel enclosures, supervised. (Not necessary if housing is recess-mounted.)

Firewolf Addressable Peripherals

FWC-FSLC-SMK
  • Addressable Analog SLC Smoke, photoelectric, head**
FWC-FSLC-HEAT
  • Addressable Analog SLC Heat, 135ºF, head**
FWC-FSLC-DUCT
  • Addressable SLC Duct smoke detector, photoelectric
FWC-FSLC-DUCTRA
  • Remote Indicator Plate with LED indicator & key reset.
FWC-FSLC-EZM2
  • Addressable SLC 2-zone conventional expansion module. Uses one address on SLC loop, but yields 2 indepent contact monitoring circuits, for pull stations, water flow and other dry contact alarm initiating devices.
FWC-FSLC-EZM1
  • Addressable SLC 1-input conventional module, similar to usage above.
FWC-FSLC-CZM
  • Addressable SLC single module, for montoring of dry contacts, ie., pull stations and conv. smokes
FWC-FSLC-RM2
  • Addressable SLC 2-output module (requires 1 SLC address)
FWC-FSLC-ISO
  • Addressable SLC Short Circuit Module. (Optional use, for certain apps. only; meets Class A, Style 7 loop reqts.)
FWC-FSLC-SOM1
  • Addressable SLC Fire supervised output module. Application examples: elevator recall, HVAC shutdown, add'l NAC output with power supply
FWC-FSLC-PULL
  • Addressable SLC Fire Pull Station
FWC-FSLC-PULLK
  • Addressable SLC Pull Station, key reset
FWC-FSLC-PROG2
  • Tool for address-programming SLC devices
FWC-FSLC-SMK6B
  • ** Smoke/Heat 6" Base, required for FWC-FSLC- SMK and –HEAT devices

Options

GEMC-12V2APS-CF
  • 12VDC Power Supply for Fire Bus, remote supervised. Direct 120VAC connection, supports 2ea. 12V, 7Ah standby batteries.
GEMC-12V2APS-R
  • 12VDC Power Supply for Burg. Bus, remote supervised. Powered by supplied 16.5V, 50VA plug-in transformer, supports 2ea. 12V, 7AH standby batteries.
GEMC-NAC6
  • Remote 4-output NAC Extender, for 6.5A ttl, or 2A, max. on any 1 output. Red 14 x 16" can, connects to 120VAC, supports 32Ah standby batts. Supervised, fire bus connection. System Sensor and Wheelock NAC synch. (5 per system, for 20 add’l NAC circuits total.)
GEM-ACM1D
  • Access Control Module (with power supply, provision for back up battery, in enclosure, plug-in transformer), 1 door kit
GEM-2D
  • Access Add-on 2 door plug–in PCB for expansion of door capacity in above.
GEMC-KEYSWKIT Keyswitch Kit
  • To be used in cases where it is required that a keyswitch be used to unlock the fire keypad. The GEMC-KEYSWKIT consists of an easy-to-install keypad / keyswitch mounting box that allows codeless locking and unlocking of the Napco GEM-FK1 Fire alarm keypad. The GEMC-KEYSWKIT is designed to be mounted to a one, two or three-gang electrical box, or to a hollow wall using mounting hardware appropriate for the mounting surface. The keyswitch is wired into one of two existing GEMC-FK1 keypad inputs; when the key is inserted and rotated, the keyswitch closes, triggering a keypad command to the control panel to unlock that keypad.
  • This feature may be configured to allow either a maintained or momentary keyswitch closure to unlock the keypad for a 15 minute period OR a maintained keyswitch closure which will unlock the keypad when opened will lock the keypad when closed
GEMC-LOCK-CAT30 Key-Alike
  • To be used in cases where it is required that the same key used to reset the pull stations also be used to unlock the control panel enclosure. Simply replace the standard enclosure lock with the GEMC-LOCK-CAT30 to "key alike" the pull station and enclosure lock. Note - the GEMC-KEYSWKIT, above is also keyed to CAT 30, allowing one key to unlock the keypad, reset the pull stations and open the GEMC control panel enclosure.
FN-CTM City Tie Module
  • The FN-CTM is a City Tie Module used to connect the GEMC Fire Alarm Control Panel to a Local Energy type City Tie Monitoring circuit. The FN-CTM City Tie Module circuit provides the power necessary to trip the Master Box Trip Coil when the Fire Alarm Control Panel goes into alarm. The City Tie Circuit is capable of providing 1A for 0.5 seconds to operate the Master Box Trip Coil. The wiring is supervised to the Master Box by placing the EOL resistor device on the terminals of the FN-CTM City Tie Module.